The information in this
document provides guidance to users of the Uniform Fire Prevention and Building
Code (Uniform Code) and the Energy Conservation Construction Code (Energy Code)
concerning the intentions and application of these codes. As with any project having the broad scope
of the Uniform Code and Energy Code revisions, editorial and technical
corrections that should have been incorporated into the codes were not caught
early enough for them to have been included in the rule making actions and
subsequent publication of the referenced documents. While the documents referenced in Title 19 NYCRR are the
applicable regulations, and contain the legally enforceable requirements for
construction, fire prevention, energy conservation and maintenance of buildings
and structures, the information provided herein is necessary to a more complete
understanding of the intent and purpose of the codes.
The attached information
can be classified into three categories, as follows:
Published ICC
Errata. The International Code Council periodically publishes errata to
the International Codes. It was
intended to incorporate all of these corrections into the Codes of New York
State, but in some cases they were inadvertently omitted during
proofreading.
Unpublished
Corrections to the ICC Codes. During the course of post-publication
review, additional typographical and other errors were discovered in those
portions of the International Codes that became the basis of the Uniform Code
and Energy Code. In addition to being
published in this document, they have also been forwarded to appropriate ICC
staff.
Uniform Code and
Energy Code Clarifications. In adapting the International Codes for use
by the State of New York, certain sections, tables and figures were deleted and
certain new text was added. These
changes were intended to remove information not applicable within New York
State, conform with statutory requirements of the Uniform Code Act and other
legislation, and incorporate New York initiatives into the code. Unfortunately, a small number of editorial
and cross-referencing errors were published in the documents referenced in
Title 19.
It is the intention of the
Department of State to recommend that the Code Council incorporate these
changes into the Uniform Code and the Energy Code by rule making actions at an
appropriate time. However, the
published codes currently referenced in Title 19 NYCRR 1220 et. seq. remain the
legally enforceable regulations until such time as that process has been
completed.
RESIDENTIAL CODE CLARIFICATIONS
R102.5 R102.5 Appendices. Revise to delete Appendix D, Recommended Practice for Safety
Inspection of an Existing Appliance Installation.
Appendix D was not included in code adoption.
R301.2.2.1.1 R301.2.2.1.1 Alternate
determination of seismic design category.
Revise the 8th line: A... SDS, for a site can shall
be ...@
Revise for consistency with code format.
R301.2.2.2 R301.2.2.2 Determination of seismic design category. Revise next to last line: A...
values in Tables R602.10.3 R602.10.1 and R603.7.@
Typographical error.
R301.2.2.6 R301.2.2.6 Height limitation in Seismic design category
D1 and D2.
Revise 4th line: A... Table R602.10.3 R602.10.1. Cold-formed ...@
Typographical error.
R317.1 R317.1 Single- and multiple-station smoke alarms. In exception no. 3, revise 2nd
line: A... basements and cellars but not ...@
By definition, basements include spaces that have been
regulated as cellars.
R327.1.8 R327.1.8 Manufactured housing. Revise 6th line: A...
located in identified flood ways floodways as established ...@
Typographical error.
R403.1.4 R403.1.4
Minimum depth. Revise last
line: A... 12 inches (350 305 mm) below ...@
Conversion error.
R408.1 R408.1 Ventilation. Revise 3rd line:
A... occupied by a basement or cellar) shall be
...@
By definition, basements include spaces that have been
regulated as cellars.
R503.2.1.1 Table
R503.2.1.1(1). In the row for 48/24
span rating sheathing, change the second column: A23/32, 3/48 3/4.@
Typographical error.
R602.10.11 Table
R602.10.11 Adjustment of Bracing
Amounts ... Wall Line Spacing. In 2nd
column heading, change reference: ...
Table R602.10.3 R602.10.1.
Typographical error.
R802.5 Table
802.5.1(8) Rafter Spans for Common
Lumber Species. Revise the 3rd
line of the title: A... ceiling not attached to rafters,
L/Δ=240)@
Typographical error..
R1003.1 Figure
R1003.1 Fireplace and Chimney Details. In figure at left, ABrick firebox and chimney, revise the small section, ADetail with wood material@ by deleting purge and inserting parge.
Typographical error.
AG105.2(6) AG105.2(6) Outdoor swimming pool. Revise 2nd line: A...
shall be a 1.25 2.25 inch (32 57 mm) square ...@
Correlate with Building Code.
AJ102.5 AJ102.5 Flood Hazard areas. Revise 3rd line: A...
subject to the provisions of R105.3.1.1 R301.2.4.
The referenced administrative requirements have been deleted
from the NYS code.
Errata
to the 2000 IRC, fifth printing, February 2002:
Table
2903.7 Minimum Size of Water Meters ...
:
change last word in title from VALVES to VALUES
P3201.5 Prohibited trap designs. Revise item
3: A>S= traps except as permitted under Section P3102.3.@
Errata
to the 2000 IRC, fourth printing, December 2001:
R314.9 Bulkhead enclosure stairways. Revise 6th
line: A... adjacent to the stairway does not exceed 8 feet (2438 mm) and
the grade level opening to the stairway is covered by a bulkhead ...@
Figure
R603.8.1.4(2) Strap and Blocking
Diaphragm ... : in small diagram, change A43 mil blkg@ to
A43 mil by@
Errata
to the 2000 IRC, third printing, June 2001:
Chapter
43, referenced standards.
CSA: change
A257.3M-92 to CAN/CSA A257.3M-92
202 202 Definitions.
BOUNDARY ELEMENTS. See Sections 1602.1 and
1613.1.
This term is defined in Section 1613.1 only.
307.1 Table
307.7(1) Maximum Allowable Quantity ...
Posing a Physical Hazard. Revise
row entitled AExplosives.@
|
Explosives |
Division 1.1 Division 1.2 Division 1.3 Division 1.4 Division 1.4G Division 1.5 Division 1.6 |
H-1 H-1 H-1 or H-2 H-3 H-3 H-1 H-1 |
1c,g 1c,g 5e,g 50e, g 125d,e,m 1e,g 1d,e,g |
(1)c,
g (1)c, g (5)e,g (50)e,g N/A (1)e,g N/A |
N/A N/A N/A N/A N/A N/A N/A |
3 g 1g 50g N/A 3 g N/A |
( (3) g (3) g (1)g (50)g N/A (3) g N/A |
N/A N/A N/A N/A N/A N/A N/A |
3 g 3 g 1g N/A N/A 3 g N/A |
(3)g (1)g N/A N/A 3 g N/A |
m. For gallons of liquid, divide the amount in
pounds by 10 in accordance with Section 2703.1.2 of the Fire Code of NYS.
Revised for consistency with 2001 Supplement to the
Fire Code.
307.1 Table
307.7(2) Maximum Allowable Quantity ...
Posing a Health Hazard. In row for
corrosives, revise entries for storage/gas cubic feet and use-closed
systems/gas cubic feet to: 810f,
g
Copied from ICC errata to IFC, second printing,
November 2000.
312.1 312.1 General. Revise list of Group U occupancies to delete agricultural
buildings.
Section 101.2, Exception no. 2 exempts agricultural
buildings from the Building Code.
708.1(5) 708.1 General. Revise 1st line of Item 5: AWalls separating sleeping accommodations units
in occupancies ...@
Revise for consistency in terminology.
902.1 902.1 Definitions. Add new definition: ATIRES, BULK STORAGE OF. Storage of tires
where the area available for storage exceeds 20,000 cubic feet (566 m3).@
Copied from ICC errata to IFC, first printing,
December 1999.
907.2.10.1.2 907.2.10.1.2 Groups
R-2, R-3, R-4 and I-1. Revise 2nd
line of exception no. 3: A... including basements and cellars but not ...@
By definition, basements include spaces that have been
regulated as cellars.
1003.2.4 1003.2.4 Ceiling height. Add Exception no. 6:
A6. Corridor ceilings in accordance
with Section 1207.2.@
Revise for consistency with Section 1207.2.
1003.2.13.3 1003.2.13.3 Elevators. Revise 4th line: A...
requirements of Section 211 2.27 of ASME A17.1 ...@
The referenced edition of ASME A17.1 has revised
section numbering.
1003.2.13.7.1 1003.2.13.7.1 Openness. Revise 1st line: AThe
exterior area of refuge rescue
assistance shall ...@
Initiative of ICC Code Correlation Committee.
1202.3 1202.3 Under-floor ventilation. Revise 3rd line: A...
occupied by a basement or cellar shall be ...@
By definition, basements include spaces that have been
regulated as cellars.
1615.1 1615.1 General procedure for determining maximum
considered earthquake and design spectral response accelerations. Revise 4th line of 2nd
paragraph: A... Figures 1615(1) through 1615(10) 1615(2). Where a site ...@
Figures were deleted.
1802.6 1802.6 Reports. Revise items 7 and 9:
7. Pile
and pier foundation information in accordance with Section 1807.2.1 1808.2.1.
9. Compacted
fill material properties and testing in accordance with Section 1803.4 1803.5.
Revise for consistency with ICC 2001 supplement, items
S18-00 and S46-00, respectively.
1615.1.2 Table
1615.1.2(1) Values of Site Coefficient Fa
as a Function of Site Class. In
second row of table heading, change SS#0.50 to SS=0.50,
SS#0.75 to SS=0.75, SS#1.00 to SS=1.00, and SS#1.25 to SS$1.25.
Table 1615.1.2(2)
Values of Site Coefficient FV as a Function of Site
Class. In second row of table heading change SS#0.1 to S1#0.1, S1#0.2 to S1=0.2, S1#0.3 to S1=0.3,
S1#0.4 to S1=0.4, and S1#0.5 to S1$0.5.
Typographical error.
2304.11.2.6 2304.11.2.6 Posts or
columns. Revise exception no. 1 in
2nd line: A... located in basements or cellars, supported
by ...@
By definition, basements include spaces that have been
regulated as cellars.
2306.3.1 Table
2306.3.1 Recommended Shear (Pounds per
Foot) for Wood Structural Diaphragms.
Revise 2nd line of footnote a: A... multiply value by 0.82 for species with
specific gravity of 0.42 or greater, or 0.65 for all other species. (3) For nails find shear value from table
above for nail size for actual grade and multiply value by the following
adjustment ...@
Typographical error.
2902.1 Table
2902.1 Minimum Number of Required Plumbing Facilities. In row 8, Storage occupancies, in the 7th
column (drinking fountains), delete see Section 411 of the Plumbing Code
of New York State and insert 1 per 1,000. In the 8th column (bath or shower),
delete 1 per 100 and insert (see Section 411 of the Plumbing Code
of New York State).
Typographical error.
3001.4 3001.4 Change in use. Revise 3rd line:
A...shall comply with Part XII Sections 8.6 and 8.7 of ASME A17.1.@
The referenced edition of ASME A17.1 has revised
section numbering.
3109.4 3109.4 Residential swimming pools. Delete exception: AA swimming pool with a power safety cover or a spa
with a safety cover complying with ASTM F 1346.@
Revise for consistency with section 3109.4.1.8(2).
Ch. 35 ASME: ASME A17.1-00, Safety Code for Elevators and
Escalators - with A17.1a-97 and A17.1b-98 and A17.1c-99 Addenda
Addenda were incorporated into the 2000 edition of the
standard.
EWA: EWS X445-97, Glulam in Residential
Construction - Southern Edition 2306.1
Referenced standard omitted in NYS printing.
K702.2.3 K702.2.3 Single exit buildings. Revise 2nd line of Item 1: A...
Section 1005.2.2 of the Fire Building Code.@
Section 1005 originates in the Building Code.
K702.4.1 K702.4.1 Exit access doorways. Revise 2nd line of Item 1: A...
Table 1004.2.1 of the Fire Building Code.@
Revise 2nd line of exception no. 3 of Item
2: A...
Section 1004.2.3.2 of the Fire Building Code of I-2
occupancies.@
Section 1005 originates in the Building Code.
K704.1 K704.1 General. Revise 3rd line:
A... Section 704 of the Fire Building
Code.@
By reference to Chapter K6 in K701.2, section K601.3
requires newly constructed elements to conform to requirements of the Building
Code.
K704.2 K704.2 Existing vertical openings. Revise 4th line of Exceptions
2.2.1 and 3.3.2: A... requirements of Section 1002.1 1009
of the Building ...@
Typographical error.
K802.3.3 K802.3.3 Fire Barriers. Revise 5th line:
A... Section K302.3 302.3 (Mixed
Occupancies) of the Building ...@
Typographical error.
ICC
Errata to the 2000 IBC, third printing (updated
March 29, 2002); the following were not
printed in the BCNYS:
311.3 Low-hazard storage, Group S-2. Revise 7th
line: A... include, but are only not limited to ...@
506.1 General. Revise If: AArea
increase due to frontage (percent) as calculated ...@
506.2 Frontage increase. Revise If: AArea
increase due to frontage (percent).
506.3 Automatic sprinkler system increase. Revise 5th
line: A... 200 percent (Is = 200 percent) for
multi-story ... and 300 percent (Is = 300 percent) for
single-story ...@
Table
601 Fire-resistance Requirements ...
Elements. At requirement for roof construction under Type IIB, delete the
reference to note Ac.@
Table
719.1(2) Rated Fire-resistance Periods ... Partitions. In Items
12-1.3 and 12-1.4, delete reference to note Af.@ In note Af,@ change
reference from AItem 6" to AItem
3.@
Table
1505.1 Minimum Roof ... Construction. In last line
of note Ac,@ change
reference from A1505.6" to A1505.7.@
1509.2.1 Type of construction. Revise 8th
line of Exception 1: A... 20 feet (6096 mm) or greater shall be ...@ Revise 7th
line of Exception 2: A... of over 20 feet (6096 mm) or greater
from a ...@
1605.4 Special seismic load combinations. Revise 5th
and 7th lines: A... resist the forces due to calculated
using Formula 16-19 ... forces and those calculated using Formula
16-20 ...@
Table
1607.1 Minimum Uniformly ... Live
Loads. In item 24, delete Aand
canopies.@
1607.4 Concentrated loads. In 3rd
line change referenced section from A1607.2"
to A1607.3.@
Table
1609.1.4 Windborne Debris ...
Structural Panels. In heading for the 3rd column,
change symbol after A2 feet@ from A#@ to A<.@
Table
1609.6.2.1(2) Component and ...
Exposure B. For roof >10 to 30 degrees, Zone 3, Wind Area 20, Wind Speed
130, change load from A-53.5" to A-53.3.@
1617.4.1.1 Calculation of seismic response coefficient. In
definitions following Equation 16-38, revise S1: AThe
mapped maximum considered ...@
Table
1904.4.1 Maximum Chloride ...
Reinforcement. In 2nd column heading, change
chemical symbol for chlorine from ACL@ to ACl.@
2109.1.1 Limitations. Revise 3rd
line of item 2: A... 110 mph ( 145 km/h 48.4 m/s).@
2110.1.1 Limitations. Revise 3rd
line and 9th line: A... fire separation assemblies barriers
or fire ... used in fire separation assemblies barriers that are
...@ Revise 3rd
line of Exception 2: A... protectives in fire separation assemblies barriers
or in fire ...@
Table
2304.6.1 Minimum Thickness fo Wall
Sheathing. In row for fiberboard, change minimum thickness from A12 inch= to A2 inch.@
2306.1 Allowable stress design. At referenced
standard ATPI 1,@ delete
referenced year A1995.@
Table
2306.4.1 Allowable Shear ... Seismic
Loading. Add reference to note Af@ at the following locations:
structural
1 sheathing, 7/16 nominal panel thickness, 13/8
fastener penetration, panel applied over gypsum sheathing, 3 inch edge spacing,
550;
sheathing,
plywood siding, 3/8 nominal panel thickness, 13/8
fastener penetration, panels applied direct to framing with 8d galvanized
casing nails, 3 inch edge spacing, 310.
Delete
reference to note Af@ at the
following locations:
structural
1 sheathing, 15/32 nominal panel thickness, 13/8
fastener penetration, panels applied direct to framing, 3 inch edge spacing,
550;
sheathing,
plywood siding, 15/32 nominal panel thickness, 13/8
fastener penetration, panels applied direct to framing, 3 inch edge spacing,
490.
Revise
note Ac@: A3/8 panel thickness or siding with
a span rating of 16 inches o.c. is ...@
2308.2 Limitations. Revise item 4
and exception: AWind speeds shall not exceed 100 mph (161 km/hr
44 m/s).
Exception: wind speeds
shall not exceed 110 mph (177 km/hr 48.4 m/s) 3-second ...@
Table
2308.9.5 Header and Girder Spans ...
Bearing Walls. Revise 3rd line of table heading:
A(Maximum header spans ...)@
Change
header spans and number of jack studs required for A4-2x8" headers, as follows:
|
HEADERS SUPPORTING |
SIZE |
GROUND SNOW LOAD
(psf)e |
|||||||||||
|
30 |
50 |
||||||||||||
|
Building Widthc
(feet) |
|||||||||||||
|
20 |
28 |
36 |
20 |
28 |
36 |
||||||||
|
Span |
NJd |
Span |
NJd |
Span |
NJd |
Span |
NJd |
Span |
NJd |
Span |
NJd |
||
|
Roof & Ceiling |
4-2x8 |
9-2 |
1 |
8-4 |
1 |
7-8 |
1 |
8-4 |
1 |
7-5 |
|||