The information in this
document provides guidance to users of the Uniform Fire Prevention and Building
Code (Uniform Code) and the Energy Conservation Construction Code (Energy Code)
concerning the intentions and application of these codes. As with any project having the broad scope
of the Uniform Code and Energy Code revisions, editorial and technical
corrections that should have been incorporated into the codes were not caught
early enough for them to have been included in the rule making actions and
subsequent publication of the referenced documents. While the documents referenced in Title 19 NYCRR are the
applicable regulations, and contain the legally enforceable requirements for
construction, fire prevention, energy conservation and maintenance of buildings
and structures, the information provided herein is necessary to a more complete
understanding of the intent and purpose of the codes.
The attached information
can be classified into three categories, as follows:
Published ICC
Errata. The International Code Council periodically publishes errata to
the International Codes. It was
intended to incorporate all of these corrections into the Codes of New York
State, but in some cases they were inadvertently omitted during
proofreading.
Unpublished
Corrections to the ICC Codes. During the course of post-publication
review, additional typographical and other errors were discovered in those
portions of the International Codes that became the basis of the Uniform Code
and Energy Code. In addition to being
published in this document, they have also been forwarded to appropriate ICC
staff.
Uniform Code and
Energy Code Clarifications. In adapting the International Codes for use
by the State of New York, certain sections, tables and figures were deleted and
certain new text was added. These
changes were intended to remove information not applicable within New York
State, conform with statutory requirements of the Uniform Code Act and other
legislation, and incorporate New York initiatives into the code. Unfortunately, a small number of editorial
and cross-referencing errors were published in the documents referenced in
Title 19.
It is the intention of the
Department of State to recommend that the Code Council incorporate these
changes into the Uniform Code and the Energy Code by rule making actions at an
appropriate time. However, the
published codes currently referenced in Title 19 NYCRR 1220 et. seq. remain the
legally enforceable regulations until such time as that process has been
completed.
RESIDENTIAL CODE CLARIFICATIONS
R102.5 R102.5 Appendices. Revise to delete Appendix D, Recommended Practice for Safety
Inspection of an Existing Appliance Installation.
Appendix D was not included in code adoption.
R301.2.2.1.1 R301.2.2.1.1 Alternate
determination of seismic design category.
Revise the 8th line: A... SDS, for a site can shall
be ...@
Revise for consistency with code format.
R301.2.2.2 R301.2.2.2 Determination of seismic design category. Revise next to last line: A...
values in Tables R602.10.3 R602.10.1 and R603.7.@
Typographical error.
R301.2.2.6 R301.2.2.6 Height limitation in Seismic design category
D1 and D2.
Revise 4th line: A... Table R602.10.3 R602.10.1. Cold-formed ...@
Typographical error.
R317.1 R317.1 Single- and multiple-station smoke alarms. In exception no. 3, revise 2nd
line: A... basements and cellars but not ...@
By definition, basements include spaces that have been
regulated as cellars.
R327.1.8 R327.1.8 Manufactured housing. Revise 6th line: A...
located in identified flood ways floodways as established ...@
Typographical error.
R403.1.4 R403.1.4
Minimum depth. Revise last
line: A... 12 inches (350 305 mm) below ...@
Conversion error.
R408.1 R408.1 Ventilation. Revise 3rd line:
A... occupied by a basement or cellar) shall be
...@
By definition, basements include spaces that have been
regulated as cellars.
R503.2.1.1 Table
R503.2.1.1(1). In the row for 48/24
span rating sheathing, change the second column: A23/32, 3/48 3/4.@
Typographical error.
R602.10.11 Table
R602.10.11 Adjustment of Bracing
Amounts ... Wall Line Spacing. In 2nd
column heading, change reference: ...
Table R602.10.3 R602.10.1.
Typographical error.
R802.5 Table
802.5.1(8) Rafter Spans for Common
Lumber Species. Revise the 3rd
line of the title: A... ceiling not attached to rafters,
L/Δ=240)@
Typographical error..
R1003.1 Figure
R1003.1 Fireplace and Chimney Details. In figure at left, ABrick firebox and chimney, revise the small section, ADetail with wood material@ by deleting purge and inserting parge.
Typographical error.
AG105.2(6) AG105.2(6) Outdoor swimming pool. Revise 2nd line: A...
shall be a 1.25 2.25 inch (32 57 mm) square ...@
Correlate with Building Code.
AJ102.5 AJ102.5 Flood Hazard areas. Revise 3rd line: A...
subject to the provisions of R105.3.1.1 R301.2.4.
The referenced administrative requirements have been deleted
from the NYS code.
Errata
to the 2000 IRC, fifth printing, February 2002:
Table
2903.7 Minimum Size of Water Meters ...
:
change last word in title from VALVES to VALUES
P3201.5 Prohibited trap designs. Revise item
3: A>S= traps except as permitted under Section P3102.3.@
Errata
to the 2000 IRC, fourth printing, December 2001:
R314.9 Bulkhead enclosure stairways. Revise 6th
line: A... adjacent to the stairway does not exceed 8 feet (2438 mm) and
the grade level opening to the stairway is covered by a bulkhead ...@
Figure
R603.8.1.4(2) Strap and Blocking
Diaphragm ... : in small diagram, change A43 mil blkg@ to
A43 mil by@
Errata
to the 2000 IRC, third printing, June 2001:
Chapter
43, referenced standards.
CSA: change
A257.3M-92 to CAN/CSA A257.3M-92
202 202 Definitions.
BOUNDARY ELEMENTS. See Sections 1602.1 and
1613.1.
This term is defined in Section 1613.1 only.
307.1 Table
307.7(1) Maximum Allowable Quantity ...
Posing a Physical Hazard. Revise
row entitled AExplosives.@
|
Explosives |
Division 1.1 Division 1.2 Division 1.3 Division 1.4 Division 1.4G Division 1.5 Division 1.6 |
H-1 H-1 H-1 or H-2 H-3 H-3 H-1 H-1 |
1c,g 1c,g 5e,g 50e, g 125d,e,m 1e,g 1d,e,g |
(1)c,
g (1)c, g (5)e,g (50)e,g N/A (1)e,g N/A |
N/A N/A N/A N/A N/A N/A N/A |
3 g 1g 50g N/A 3 g N/A |
( (3) g (3) g (1)g (50)g N/A (3) g N/A |
N/A N/A N/A N/A N/A N/A N/A |
3 g 3 g 1g N/A N/A 3 g N/A |
(3)g (1)g N/A N/A 3 g N/A |
m. For gallons of liquid, divide the amount in
pounds by 10 in accordance with Section 2703.1.2 of the Fire Code of NYS.
Revised for consistency with 2001 Supplement to the
Fire Code.
307.1 Table
307.7(2) Maximum Allowable Quantity ...
Posing a Health Hazard. In row for
corrosives, revise entries for storage/gas cubic feet and use-closed
systems/gas cubic feet to: 810f,
g
Copied from ICC errata to IFC, second printing,
November 2000.
312.1 312.1 General. Revise list of Group U occupancies to delete agricultural
buildings.
Section 101.2, Exception no. 2 exempts agricultural
buildings from the Building Code.
708.1(5) 708.1 General. Revise 1st line of Item 5: AWalls separating sleeping accommodations units
in occupancies ...@
Revise for consistency in terminology.
902.1 902.1 Definitions. Add new definition: ATIRES, BULK STORAGE OF. Storage of tires
where the area available for storage exceeds 20,000 cubic feet (566 m3).@
Copied from ICC errata to IFC, first printing,
December 1999.
907.2.10.1.2 907.2.10.1.2 Groups
R-2, R-3, R-4 and I-1. Revise 2nd
line of exception no. 3: A... including basements and cellars but not ...@
By definition, basements include spaces that have been
regulated as cellars.
1003.2.4 1003.2.4 Ceiling height. Add Exception no. 6:
A6. Corridor ceilings in accordance
with Section 1207.2.@
Revise for consistency with Section 1207.2.
1003.2.13.3 1003.2.13.3 Elevators. Revise 4th line: A...
requirements of Section 211 2.27 of ASME A17.1 ...@
The referenced edition of ASME A17.1 has revised
section numbering.
1003.2.13.7.1 1003.2.13.7.1 Openness. Revise 1st line: AThe
exterior area of refuge rescue
assistance shall ...@
Initiative of ICC Code Correlation Committee.
1202.3 1202.3 Under-floor ventilation. Revise 3rd line: A...
occupied by a basement or cellar shall be ...@
By definition, basements include spaces that have been
regulated as cellars.
1615.1 1615.1 General procedure for determining maximum
considered earthquake and design spectral response accelerations. Revise 4th line of 2nd
paragraph: A... Figures 1615(1) through 1615(10) 1615(2). Where a site ...@
Figures were deleted.
1802.6 1802.6 Reports. Revise items 7 and 9:
7. Pile
and pier foundation information in accordance with Section 1807.2.1 1808.2.1.
9. Compacted
fill material properties and testing in accordance with Section 1803.4 1803.5.
Revise for consistency with ICC 2001 supplement, items
S18-00 and S46-00, respectively.
1615.1.2 Table
1615.1.2(1) Values of Site Coefficient Fa
as a Function of Site Class. In
second row of table heading, change SS#0.50 to SS=0.50,
SS#0.75 to SS=0.75, SS#1.00 to SS=1.00, and SS#1.25 to SS$1.25.
Table 1615.1.2(2)
Values of Site Coefficient FV as a Function of Site
Class. In second row of table heading change SS#0.1 to S1#0.1, S1#0.2 to S1=0.2, S1#0.3 to S1=0.3,
S1#0.4 to S1=0.4, and S1#0.5 to S1$0.5.
Typographical error.
2304.11.2.6 2304.11.2.6 Posts or
columns. Revise exception no. 1 in
2nd line: A... located in basements or cellars, supported
by ...@
By definition, basements include spaces that have been
regulated as cellars.
2306.3.1 Table
2306.3.1 Recommended Shear (Pounds per
Foot) for Wood Structural Diaphragms.
Revise 2nd line of footnote a: A... multiply value by 0.82 for species with
specific gravity of 0.42 or greater, or 0.65 for all other species. (3) For nails find shear value from table
above for nail size for actual grade and multiply value by the following
adjustment ...@
Typographical error.
2902.1 Table
2902.1 Minimum Number of Required Plumbing Facilities. In row 8, Storage occupancies, in the 7th
column (drinking fountains), delete see Section 411 of the Plumbing Code
of New York State and insert 1 per 1,000. In the 8th column (bath or shower),
delete 1 per 100 and insert (see Section 411 of the Plumbing Code
of New York State).
Typographical error.
3001.4 3001.4 Change in use. Revise 3rd line:
A...shall comply with Part XII Sections 8.6 and 8.7 of ASME A17.1.@
The referenced edition of ASME A17.1 has revised
section numbering.
3109.4 3109.4 Residential swimming pools. Delete exception: AA swimming pool with a power safety cover or a spa
with a safety cover complying with ASTM F 1346.@
Revise for consistency with section 3109.4.1.8(2).
Ch. 35 ASME: ASME A17.1-00, Safety Code for Elevators and
Escalators - with A17.1a-97 and A17.1b-98 and A17.1c-99 Addenda
Addenda were incorporated into the 2000 edition of the
standard.
EWA: EWS X445-97, Glulam in Residential
Construction - Southern Edition 2306.1
Referenced standard omitted in NYS printing.
K702.2.3 K702.2.3 Single exit buildings. Revise 2nd line of Item 1: A...
Section 1005.2.2 of the Fire Building Code.@
Section 1005 originates in the Building Code.
K702.4.1 K702.4.1 Exit access doorways. Revise 2nd line of Item 1: A...
Table 1004.2.1 of the Fire Building Code.@
Revise 2nd line of exception no. 3 of Item
2: A...
Section 1004.2.3.2 of the Fire Building Code of I-2
occupancies.@
Section 1005 originates in the Building Code.
K704.1 K704.1 General. Revise 3rd line:
A... Section 704 of the Fire Building
Code.@
By reference to Chapter K6 in K701.2, section K601.3
requires newly constructed elements to conform to requirements of the Building
Code.
K704.2 K704.2 Existing vertical openings. Revise 4th line of Exceptions
2.2.1 and 3.3.2: A... requirements of Section 1002.1 1009
of the Building ...@
Typographical error.
K802.3.3 K802.3.3 Fire Barriers. Revise 5th line:
A... Section K302.3 302.3 (Mixed
Occupancies) of the Building ...@
Typographical error.
ICC
Errata to the 2000 IBC, third printing (updated
March 29, 2002); the following were not
printed in the BCNYS:
311.3 Low-hazard storage, Group S-2. Revise 7th
line: A... include, but are only not limited to ...@
506.1 General. Revise If: AArea
increase due to frontage (percent) as calculated ...@
506.2 Frontage increase. Revise If: AArea
increase due to frontage (percent).
506.3 Automatic sprinkler system increase. Revise 5th
line: A... 200 percent (Is = 200 percent) for
multi-story ... and 300 percent (Is = 300 percent) for
single-story ...@
Table
601 Fire-resistance Requirements ...
Elements. At requirement for roof construction under Type IIB, delete the
reference to note Ac.@
Table
719.1(2) Rated Fire-resistance Periods ... Partitions. In Items
12-1.3 and 12-1.4, delete reference to note Af.@ In note Af,@ change
reference from AItem 6" to AItem
3.@
Table
1505.1 Minimum Roof ... Construction. In last line
of note Ac,@ change
reference from A1505.6" to A1505.7.@
1509.2.1 Type of construction. Revise 8th
line of Exception 1: A... 20 feet (6096 mm) or greater shall be ...@ Revise 7th
line of Exception 2: A... of over 20 feet (6096 mm) or greater
from a ...@
1605.4 Special seismic load combinations. Revise 5th
and 7th lines: A... resist the forces due to calculated
using Formula 16-19 ... forces and those calculated using Formula
16-20 ...@
Table
1607.1 Minimum Uniformly ... Live
Loads. In item 24, delete Aand
canopies.@
1607.4 Concentrated loads. In 3rd
line change referenced section from A1607.2"
to A1607.3.@
Table
1609.1.4 Windborne Debris ...
Structural Panels. In heading for the 3rd column,
change symbol after A2 feet@ from A#@ to A<.@
Table
1609.6.2.1(2) Component and ...
Exposure B. For roof >10 to 30 degrees, Zone 3, Wind Area 20, Wind Speed
130, change load from A-53.5" to A-53.3.@
1617.4.1.1 Calculation of seismic response coefficient. In
definitions following Equation 16-38, revise S1: AThe
mapped maximum considered ...@
Table
1904.4.1 Maximum Chloride ...
Reinforcement. In 2nd column heading, change
chemical symbol for chlorine from ACL@ to ACl.@
2109.1.1 Limitations. Revise 3rd
line of item 2: A... 110 mph ( 145 km/h 48.4 m/s).@
2110.1.1 Limitations. Revise 3rd
line and 9th line: A... fire separation assemblies barriers
or fire ... used in fire separation assemblies barriers that are
...@ Revise 3rd
line of Exception 2: A... protectives in fire separation assemblies barriers
or in fire ...@
Table
2304.6.1 Minimum Thickness fo Wall
Sheathing. In row for fiberboard, change minimum thickness from A12 inch= to A2 inch.@
2306.1 Allowable stress design. At referenced
standard ATPI 1,@ delete
referenced year A1995.@
Table
2306.4.1 Allowable Shear ... Seismic
Loading. Add reference to note Af@ at the following locations:
structural
1 sheathing, 7/16 nominal panel thickness, 13/8
fastener penetration, panel applied over gypsum sheathing, 3 inch edge spacing,
550;
sheathing,
plywood siding, 3/8 nominal panel thickness, 13/8
fastener penetration, panels applied direct to framing with 8d galvanized
casing nails, 3 inch edge spacing, 310.
Delete
reference to note Af@ at the
following locations:
structural
1 sheathing, 15/32 nominal panel thickness, 13/8
fastener penetration, panels applied direct to framing, 3 inch edge spacing,
550;
sheathing,
plywood siding, 15/32 nominal panel thickness, 13/8
fastener penetration, panels applied direct to framing, 3 inch edge spacing,
490.
Revise
note Ac@: A3/8 panel thickness or siding with
a span rating of 16 inches o.c. is ...@
2308.2 Limitations. Revise item 4
and exception: AWind speeds shall not exceed 100 mph (161 km/hr
44 m/s).
Exception: wind speeds
shall not exceed 110 mph (177 km/hr 48.4 m/s) 3-second ...@
Table
2308.9.5 Header and Girder Spans ...
Bearing Walls. Revise 3rd line of table heading:
A(Maximum header spans ...)@
Change
header spans and number of jack studs required for A4-2x8" headers, as follows:
|
HEADERS SUPPORTING |
SIZE |
GROUND SNOW LOAD
(psf)e |
|||||||||||
|
30 |
50 |
||||||||||||
|
Building Widthc
(feet) |
|||||||||||||
|
20 |
28 |
36 |
20 |
28 |
36 |
||||||||
|
Span |
NJd |
Span |
NJd |
Span |
NJd |
Span |
NJd |
Span |
NJd |
Span |
NJd |
||
|
Roof & Ceiling |
4-2x8 |
9-2 |
1 |
8-4 |
1 |
7-8 |
1 |
8-4 |
1 |
7-5 |
1 |
6-8 |
1 |
|
Roof, Ceiling & 1 Center-Bearing Floor |
4-2x8 |
8-1 |
1 |
7-3 |
1 |
6-7 |
1 |
7-5 |
1 |
6-6 |
1 |
5-11 |
2 |
|
Roof, Ceiling & 1 Clear Span Floor |
4-2x8 |
7-2 |
1 |
6-3 |
2 |
5-7 |
2 |
7-0 |
1 |
6-1 |
2 |
5-6 |
2 |
|
Roof, Ceiling & 2 Center-Bearing Floors |
4-2x8 |
6-10 |
1 |
6-0 |
2 |
5-5 |
2 |
6-8 |
1 |
5-10 |
2 |
5-3 |
2 |
|
Roof, Ceiling & 2 Clear Span Floors |
4-2x8 |
5-7 |
2 |
4-10 |
2 |
4-4 |
2 |
5-6 |
2 |
4-9 |
2 |
4-3 |
2 |
Table
2308.9.6 Header and Girder Spans for Interior Bearing Walls. Revise 3rd
line of table heading: A(Maximum
header spans ...)@
Change
header spans and number of jack studs required for A4-2x8" headers, as follows:
|
HEADERS AND
GIRDERS SUPPORTING |
SIZE |
BUILDING WIDTHC
(feet) |
|||||
|
20 |
28 |
36 |
|||||
|
Span |
NJd |
Span |
NJd |
Span |
NJd |
||
|
One Floor Only |
4-2x8 |
9-0 |
1 |
7-8 |
1 |
6-9 |
1 |
|
Two Floors |
4-2x8 |
6-1 |
1 |
5-3 |
2 |
4-8 |
2 |
Ch.
35. NFPA 285-98. Revise name
of standard: AStandard Method of ... Using the International Intermediate
Scale, ...@
Table
E104.2 Accessible Beds. Revise 1st
column, last row: AOver 1,001 and
over@
ICC
Errata to the 2000 IBC, second printing (updated
January 01, 2002); the following were
not printed in the BCNYS:
Section
202 DEFINITIONS.
CONSTRUCTION
TYPES. Add: AType V. See Section 602.5.@
LOADS. Add: AGravity
Load (W). See Section 1613.1.@
406.3.11 Enclosure of vertical openings. Revise 3rd
line: A... specified in Section 406.2.8. 406.3.8.@
Table
704.8 Maximum Area of Exterior Wall
Openings. Revise references to footnotes:
In
column heading for 3-5 feet, delete reference to footnote f.
In
column heading for 5-10 feet, delete reference to footnote b.
In
column heading for 10-15 feet, delete reference to footnote b.
707.2 Shaft enclosure required. Revise 3rd
line of exception no. 4: A... in accordance with Section 711.4.4 711.4.@
909.8.5 Plume Contact with walls. Delete
existing equations for Tc and SI: Tc and substitute the
following:
Tc
= .60(Ta + 460)Qc2/3z-5/3 + Ta
SI:
Tc = .08TaQc2/3z-5/3 + Ta
Table
1004.3.2.1 Corridor Fire Resistance
Rating. For occupancy R (4th row), revise second column: AGreater
than 30 10.@
1005.3.6.5 Exterior stairway protection. Revise 3rd
line of exception no. 4: A... connected to open-ended corridors, provided that Items
4.1 through 4.4 are met.@
Table
1604.5 Classification of Buildings and
Other Structures for Importance Factor. Revise Category III, 6th bullet
point: A... material exceeds the exempt amounts maximum allowable
quantities of Table 307.7(2).@
2103.2 Clay or shale masonry units. Revise 3rd
line: A... load-bearing wall file tile; ASTM C56 for structural clay nonload-bearing
wall tie tile; ...@
2104.3 Cold weather construction. Revise 3rd
line of Item 4: A... heat sources shall be used in to
maintain temperatures above ...@
2113.7 Offsets. Revise last line: A...
specified in Section 2113.2 2113.5.@
2304.10.2 Floor framing. Revise 4th
line: A... walls. Where immediate
intermediate beams are used ...@
2306.4.3 Particle board shear walls. On page 532,
revise 6th line: ... Aspaced 24 inches (610 mm) on center, nails shall be
spaced 6 inches (152 mm) on center along intermediate ...@
Table
2308.10.9 Allowable Spans for 2-inch
Tongue and Groove Decking. Revise note a: A... on a 12 inch width of floor decking. Random lay up ...@
2511.1.1 Installation. Revise 3rd
line: A... and Section 2508 2507.@
ICC
Errata to the 2000 IBC, first printing, March 2000; the
following were not printed in the BCNYS:
Table
307.7(1) Maximum Allowable Quantity per
Control Area of Hazardous Materials Posing a Physical Hazard. Revise
Oxidizer, Class 4, Storage, Solid pounds to 1e, g
402.7.1 Attached garage. Revise 4th
line: A... considered as separate buildings where ...@
508.2 Group S-2 enclosed parking garages with
Groups A, B, M, or R above. Revise 4th line of Item 2: A...less
than 300, or Group B, M or R.@
In
item 3, exception no. 2, revise 3rd line: A...less than 300, or Group B or and M
shall ...@
714.3 Fire-protection-rated glazing. Revise last
line: A... Section 714.2.6. 714.3.7.@
1605.1 General. Revise 5th
line: A... 1620.1.6, 1620.1 1620.1.9
or ...@
Table
1621.3 Mechanical and Electrical
Components Coefficients. Revise table headings in two right columns
from apa to (ap)a and Rp
to (Rp).
2108.9.2.11 Splices. In item 1, change AId@ to
AIld@
and revise:
AIld = Required development length of reinforcement
Minimum lap splice length, inches (mm).@
Chapter
35, Referenced Standards
AWS D1.4-98: revise section reference to 2108.9.2.11 Item
2.
Index
Bolts,
high strength steel: change reference from 1704.3.3 to 1707.4.3.3
308.5 Table
308.5 Hanger Spacing. Delete row for support of lead pipe.
Lead pipe is not an approved material in new
installations.
403.1 Table
403.1 Minimum Number of Required
Plumbing Fixtures. In row 8,
Storage occupancies, in the 7th column (drinking fountains), delete see
Section 411 and insert 1 per 1,000.
In the 8th column (bath or shower), delete 1 per 100
and insert (see Section 411).
Typographical error.
425.2 Insert deleted section and renumber
succeeding sections (no change to text):
425.2 Access
to concealed connections. Fixtures with concealed slip-joint
connections shall be provided with an access panel or utility space at least 12
inches (305 mm) in its smallest dimension or other approved arrangement so as
to provide access to the slip connections for inspection and repair.
425.2
425.3 Flushometer valves and
tanks.
425.3
425.4 Flush tanks.
425.3.1
425.4.1 Ballcocks.
425.3.2
425.4.2 Overflows in flush
tanks.
425.3.3
425.4.3 Sheet copper.
425.3.4
425.4.4 Access required.
425.4 425.5 Flush pipes and fittings.
425.4.1
425.5.1 Fill valves.
Section inadvertently omitted.
605.6 Table 605.6 Pipe Fittings. In 6th row, Copper or copper alloy, add ASME B16.32.
Coordinate with errata to the 2000 IPC, first
printing, January 2000.
702.1 Table 702.1 Above-ground Drainage and Vent Pipe. In 13th row, polyolefin pipe, add
CSA B181.6.
Coordinate with ICC errata.
702.4 Table 702.4 Pipe Fittings. In 7th row, Copper or copper alloy, add ASME B16.32.
Coordinate with errata to the 2000 IPC, first
printing, January 2000.
1102.7 Table 1102.7 Pipe Fittings. In 4th row, Copper or copper alloy, add ASME B16.32.
Coordinate with errata to the 2000 IPC, first
printing, January 2000.
Ch. 13 ASME: revise issue date for A112.21.2M from 1991
to 1983.
Correct referenced standard date.
ASSE. 1001-90:
delete 425.2, and add 425.3.
Correct section reference.
1017-99:
delete 424.4.
ASSE 1017 is not referenced in 424.4.
ASTM. C1173-97:
delete 705.21, and add 705.2.1.
Typographical error.
AWWA.
C111-90: delete 605.13, and add 605.14.
Correct section reference.
CSA. Add CSA B181.6-96, Polyolefin Laboratory
Drainage Systems, Table 702.1.
Errata to 2000 IPC, first printing, January 2000.
FS. Delete reference standard for lead pipe, FS
WW-P-325B-76.
Lead pipe is not an approved material in new
installations.
ICBO. ECCC-NYS:
change reference from 607.2 to 607.2.1.
MECHANICAL CODE CLARIFICATIONS
601.2 601.2 Air movement in egress elements. Revise 1st line:
AExit passageways and exit access corridors ...@
Correct terminology for consistency with Building
Code.
Errata
to the 2000 IMC, third printing, October 2001 (Updated August 28, 2002):
607.3.2.1 Smoke damper activation activation
methods. Revise first sentence to read:
AThe smoke damper shall close upon actuation activation
of a listed smoke detector or detectors installed in accordance with Section 606, Sections 907.10 and
907.11 of the International Fire Code of New York State and
one of the following methods, as applicable:@
Ch. 15 UL. Delete UL 300-96 as a referenced standard.
Errata
to the 2000 IMC, second printing, January 2001:
502.8.5.5 Bulk plants or terminals. Revise 3rd
line: A... received by tank vessels, pipelines, tank cars or tank vehicles
and which are stored or blended in bulk for the purpose of distributing such
liquids by tank vessels, pipelines, tanks cars, tank vehicles or containers,
as required by Sections 502.8.5.5.1 through 502.8.5.5.3.@
513.8.5 Plume contact with walls. Delete
existing equations for Tc and SI: Tc and substitute with
the following:
Tc = .60(Ta +
460)Qc2/3z-5/3 + Ta
SI: Tc = .08TaQc2/3z-5/3
+ Ta
Errata
to the 2000 IFGC, third printing, March 2001:
101.2 Scope. After 1st item 4,
add:
Exception: Detached one-
and two-family dwellings and multiple single-family dwellings (townhouses) not
more than three stories high with separate means of egress and their accessory
structures shall comply with the Residential Code of NYS.
306.2 Appliances in rooms. Revise 3rd
line: ... not less than 35 36
inches (889 914 mm) wide ...
Ch.
7, Referenced Standards. Below the chapter title, add the following:
This chapter lists the standards that
are referenced in various sections of this document. The standards are listed herein by the promulgating agency of the
standard, the standard identification, the effective date and title, and the
section or sections of this document that reference the standard. The
application of the referenced standards shall be as specified in Section 102.8.
ANSI. Change address to 25 West 43rd
Street, Fourth Floor, New York, NY 10036.
Errata
to the 2000 IFGC, second printing, September 2000:
503.5.6 Inspection of chimneys. Relocate
exception from 503.5.6 to 503.5.6.1.
202 202
GENERAL DEFINITIONS. Revise
definition of OCCUPANCY CLASSIFICATION for Residential Group R:
R-1. Add new description: Motels
(transient)
R-2. Add new descriptions: Vacation
timeshare properties
Hotels (non transient)
Motels
(non transient)
R-3. Revise: AResidential
occupancies where the occupants are primarily permanent in nature and not classified
as R-1, R-2, R-4 or I, and where buildings do not contain more than two
dwelling units, or adult and child care facilities, that provide
accommodations for five or fewer persons of any age for less than 24 hours as
applicable in Section 101.2. Adult
and child care facilities that are within a single family home are permitted to
comply with the Residential Code of New York State in accordance with
Section 101.2 of the Building Code of New York State.@
R-4. Revise: AResidential
occupancies shall include buildings arranged for occupancy as Residential
Care/Assisted Living Facilities including more than five but not more than 16
occupants, excluding staff.
Group
R-4 occupancies shall meet the requirements for construction as defined for
Group R-3 except for the height and area limitations provided in Section 503
of as otherwise provided for in the Building Code of New York
State or shall comply with the Residential Code of New York State,
in accordance with Section 101.2 of the Building Code of New York State.@
Correlate with Building Code.
308.3.6 308.3.6 Group A occupancies.
Revise second line of Exception 2:
A... Chapter 6 of this code and the Mechanical
Code of New York State.@
Clarify code reference in the exception.
505.1 505.1 Address numbers. Add
exception: AException: Buildings identified under an
addressing scheme as part of an countywide 911 numbering system.@
Correlate with Property Maintenance Code.
906.1 Table 906.1 Additional Required Portable Fire
Extinguishers. Delete 29th
row: 3308.11 Fireworks.
Section 3308.11 was deleted from the Fire Code of NY.
907.2.10.1.2 907.2.10.1.2 Groups R-2, R-3, R-4 and I-1. Revise 2nd line of exception no. 3: A...
including basements and cellars but not ...@
By definition, basements include spaces that have been
regulated as cellars.
909.8.5 909.8.5 Plume Contact with walls.
Delete existing equations for Tc and SI: Tc and
substitute the following:
Tc = .60(Ta + 460)Qc2/3z-5/3
+ Ta
SI: Tc = .08TaQc2/3z-5/3
+ Ta
Correlate with Building Code.
1003.2.13.3 1003.2.13.3 Elevators. Revise 4th
line: A... requirements of Section 211 2.27 of
ASME ...@
The referenced edition of ASME A17.1 has revised
section numbering.
1003.2.13.4 1003.2.13.4 Platform lifts.
Revise section: APlatform (wheelchair) lifts shall not serve as part of
an accessible means of egress, except where allowed as part of a required
accessible route in Section 1109.7 of the Building Code of NYS. Platform lifts shall be installed in accordance
with ASME A18.1.@
Correlate with Building Code.
1003.2.13.7.1 1003.2.13.7.1 Openness. Revise 1st
line: AThe exterior area of refuge
rescue assistance shall ...@
Correlate with Building Code.
1003.3.3.9 1003.3.3.9 Spiral stairways. Delete
exception between 1st and 2nd paragraphs.
A... in accordance with Section 1007.4.1.
Exception: Spiral stairways serving
catwalks, galleries and gridirons complying with Section 1007.4.1.@
Correlate with Building Code.
1010.17.2 Table 1010.17.2 Common Path, Dead-End and Travel Distance
Limits. Revise as follows:
In row for Group B, revise common path
limit/unsprinklered to A75f@ and travel distance/sprinklered to A250 300.@
In rows for Groups F-1, S-1 and F-2, S-2, revise
common path limit/unsprinklered to A75f.@
In row for Group U, revise travel
distance/unsprinklered to A200 300" and travel distance/sprinklered to A250 400.@
Add new footnote f:
A100 feet for common path serving not more than 30
persons.@
Correlate with Building Code.
1012.3 1012.3 Capacity of means of egress.
Revise last line: A... Sections 1003.2.3, 1005.2.1 and 1008.5.@
Section reference inadvertently omitted.
1012.7.5 1012.7.5 Power source. Revise 3rd line: A...
duration of not less than 90 60 minutes in case of primary power
...@
Exception: revise 3rd line: A...
duration of not less than 90 60 minutes, in case of primary power
...@
Typographical error.
2206.8 Revise: 2206.8 Fire fueling
area protection system. A listed
automatic fire-extinguishing ...@
Revise to correct name and designation of system.
2604.3 2604.3 Area reviews.
Revise: ABefore hot work is permitted and at least once per day
while the permit is in effect during hot work operations, the
area shall be inspected by the individual responsible for authorizing hot work
operations to ensure that it is a fire safe area. Information shown on the permit shall be verified prior to
signing the permit in accordance with Section 105.6.@
There are no provisions for hot work permits in Ch. 1
of the Fire Code of NY.
2703.9.9 2703.9.9 Shelf storage. Delete
exception 2:
Exceptions: 1. Storage in hazardous material storage
cabinets or laboratory furniture specifically designed for such use.
2. Storage of
hazardous materials in amounts not requiring a permit in accordance with
Section 2701.4.
There are no provisions for permits in Section 2701.4.
2903.4 2903.4 Agricultural products.
Delete last sentence: AA permit shall not be required for agricultural
storage.@
There are no provisions for permits in the Fire Code
of NYS.
3305.9 Table 3305.9 Application of Separation Distance Table. Revise headings:
In the 2nd column heading, revise table
reference from 3304.5.2(2) to 3305.4(1).
In the 3rd column heading, revise table
reference from 3304.5.2(3) to 3305.4(2).
In the 4th column heading, revise table
reference from 3304.5.2(4) to 3305.4(3).
Tables from deleted section 3304 were retained and
renumbered.
3404.2.11.2 3404.2.11.2 Location. Revise
exception no. 2, 2nd line: A... basement, pit, cellar, or lot line ...@
By definition, basements include spaces that have been
regulated as cellars.
Ch. 45 ASME. Revise referenced edition of ASME
A17.1: A17.1- 96 00, Safety Code for Elevators and Escalators with
A17.1a-97, A17.1b-98, A17.1c-99;
A17.1d-00 Addenda.
Revise referenced edition of ASME A17.3: A17.3-96, Safety Code for Existing Elevators
and Escalators - with Addenda A17.3a- 99 00.
Correlate with Building Code.
In left hand column, insert one blank line between
A17.1 and A17.3, such that A17.3 aligns with ASafety Code for Existing ... ,@ B16.18 aligns with ACast Copper Alloy ...,@ B16.22 aligns with AWrought Copper
...,@ and ASME-98 aligns with A boiler and Pressure Vessel ...@
Correct printing error.
Add: ASME
A18.1-01, Safety Standard for Platform Lifts and Stairway Chairlifts,
1003.2.14.4.
Correlate with Building Code.
Errata
to the 2000 IFC, fourth printing (Updated March 29, 2002):
Table
2306.2 General Fire Protection and
Life-Safety Requirements. In column 2, in the last cell opposite
Commodity Class I - IV, change the footnote reference: AGreater
than 500,000h g@
Errata
to the 2000 IFC, third printing, July 2001:
803.2.1 Foam plastics, Exception 2 3rd
line: A... provided it is not more less than 20 pounds ...@
803.7.1 Upholstered furniture classification. 3rd
line: A... in accordance with NFPA 261 260.@
1003.3.1 Doors. 2nd line of 2nd
paragraph: A... adjacent construction, and finishes such
that the doors are easily recognizable as doors.@
4102
PYROPHORIC Revise last line: A... temperature of 13 130E F (-11 54E C).@
Errata
to the 2000 IFC, second printing, November 2000:
Table
2703.1.1(2) Maximum
allowable quantity per control area of hazardous Material posing a health
hazard. In row for corrosives,
revise entries for storage/gas cubic feet and use-closed systems/gas cubic feet
to: 810f, g.
PROPERTY MAINTENANCE CODE CLARIFICATIONS
302.4 302.4 Weeds. Delete 2nd
paragraph in its entirety.
The 2nd paragraph consists of
administrative provisions that are inconsistent with the scope of the Uniform
Code.
Errata
to the 2000 IPMC, second printing, February 2001:
Ch.
8.
Delete ASME and A17.1-96 from referenced standards.
101.4.1 Add new section: 101.4.1.3 Unconditioned buildings.
Buildings and structures or portions thereof which are neither heated nor
cooled.
This section of the code is referenced from section
101.4.1.
202 202
Definitions.
GROSS FLOOR AREA. Revise 2nd
line: ... basements, cellars,
mezzanines ...
By definition in the Building Code, basements include
spaces that have been regulated as cellars.
RESIDENTIAL BUILDING, R-2. Revise 3rd
line: ... in nature such as townhouses,
rowhouses, apartment houses, ...
Townhouses are defined elsewhere.
302.1 Figure 302.1. Zone County
14A 13A Dutchess
Figure 302.1 incorrectly identifies the exterior design condition zone for
Dutchess County, which is properly identified in Table 302.1.
502.2.4 Table 502.2.4(2) Prescriptive Building Envelope ... 12
Percent of Gross Exterior Wall Area.
In row for 7,000 - 8,499 heating degree days, revise entry in 3rd
column, Ceiling R-value from AE-49" to AR-49.@
Typographical error.
502.2.5 502.2.5 Prescriptive path for additions and window replacements. Revise 4th line: A...
to existing single-family residential buildings one- and two-family
dwellings and structures shall ...@
For consistency in terminology.
504.2.2 504.2.2 Combination service water-heating/space-heating boilers. Revise Equation 5-12, and revise definition
of pmd:
13.3 pmd + 400 (Equation 5-12)
n
A... Chapter 37 of the ASHRAE HVAC Systems and
Applications Handbook.@
Correct formula and title of referenced standard.
803.3.3.8 803.3.3.8 Heat rejection equipment
fan speed control. Revise exception
as follows:
Exception: Factory-installed heat rejection devices
within HVAC equipment tested and rated in accordance with Tables 803.3.2(1)
803.2.2(1) through 803.3.2(3) 803.2.2(3) and 803.3.2(2).
Revise to reference tables covering heat rejection
equipment.
805.6.1 805.6.1 Liquid‑Immersed Transformers. Revise text: ALiquid‑immersed transformers shall comply with
the minimum efficiencies in Table 805.6.1 as tested and rated in accordance
with Section 313 of the Electric Utility Industry Restructuring Act of November
25, 1997 (NEMA TP1.)@
Correct title.
Ch. 9 ASHRAE: ASHRAE-99, HVAC Systems and
Applications Handbook.
Correct title of referenced standard.
Errata
to the 2000 IECC, second printing, January 2001:
Table 502.2.1.1.2(1), Required